Multi-Gard
®
PVC – Terminations
Standard Terminators (Type 1) allow
Multi-Gard to be terminated into a
standard pre-cast termination.
1. Remove watertight plugs in order to
assure total insertion of the Multi-Gard
innerducts.
2. Install terminators into male end of
Multi-Gard to full depth.
3. Replace watertight plugs into the
terminator and tighten.
4. Insert prepared male end into the
pre-cast terminator with print line facing
upward. Solvent cement into place.
5. Use shim enclosed for terminator
requiring a connection of Type C
(4.35 O.D.) into a Type 40 (4.50 O.D.)
termination.
Use a Type 6 Enclosure Terminator at
entrances into metal or non-metallic
enclosures above ground.
1. Remove watertight plugs in order to
assure total insertion of the Multi-Gard
innerducts.
2. Install terminators into male end of
Multi-Gard to full depth.
3. Replace watertight plugs into the
terminator and tighten.
4. Install threaded adapter over end of
Multi-Gard using solvent cement. Insert
adapter through enclosure hole and
provide 4" locking ring.
5. Use shim enclosed for terminator
requiring a connection of type C (4.35
O.D.) termination.
The pass-through terminator is designed to
allow for continuous ducts through the vault
or hand hole for cable pulling.
1. Install terminator into vault following steps
1 through 5 for standard Type 1 terminator.
2. Cut innerduct of pass through kit 10" longer
than the width of the manhole. Add spacers
as needed.
3. Upon completion, remove the watertight
plugs and install innerducts to traverse
manhole/handhole by cutting to length
inserting into one side of handhole and
raising or bowing center of innerduct span
to insert into the pass-through terminator
on the opposite side. (See pass-through kits
on page 276.)
Use a Type 1 Standard Terminator also at an
entrance where a pre-cast terminator is not
available or a knockout is used:
1. Insert the male end section of Multi-Gard
4 inches past the inside wall of the vault
with print line facing upward.
2. Remove the protective cap from the male
end of the Multi-Gard.
3. Remove the watertight plugs and insert
the terminator to full depth.
4. Install bell fitting over the end of
Multi-Gard using solvent cement, and
replace plugs.
5. Slide Multi-Gard section until bell fitting is
flush with inside, and then seal entrance as
required by job specifications.
Use the jet terminator for jetting operations.
1. Remove watertight plugs in order to assure
to total insertion.
2. Apply standard grade solvent cement
(VC9962) to male end of Multi-Gard. Install
jet terminator to insertion line.
3. Replace watertight plugs into terminator
and tighten.
4. Apply standard grade solvent cement to
terminator male end and insert into pre-cast
bell end. (Install PVC bell fitting in kit if pre-
cast bell end is not available).
5. Use shim enclosed for terminator requiring
a connection of Type C (4.35" O.D.) into a
Type 40 (4.50" O.D.) termination.
6. Measure between ends of terminators on
opposite ends of vault, and cut innerduct to
length.
7. Solvent cement each coupling into place or
use mechanical coupling rated for use with
high speed air blowing systems.
Use split plugs for sealing Multi-Gard cells
where cable has been installed.
(See page 274)
Terminations
1.
3.
5.
4.
2.
6.